Liquitron Controllers
|
| DC5500 Cooling Tower Controller with
Remote Programming & Communications |
|
| DC4500 Cooling Tower
Controller |
|
| DC4000 Cooling Tower/Boiler
Controller |
|
| AC4000/5000 Cooling Tower
Controller |
|
| DP5000 pH Controller |
|
| DR5000 ORP Controller |
|
| FS5000 Flow Switch Controller |
|
DC5500 Cooling Tower Controller with
Remote Programming & Communications
The DC5500 has all of the features of the
popular DC4500 Controller(see below); dual biocides & inhibitor pumps
control, 0-20,000mS conductivity range, four feed modes, etc. The DC5500 also
has the additional features of a second water meter input, three tank level
inputs, and most importantly- communications capabilities to download
historical data, view real time conditions, and program the controller
remotely. Each DC5500 has an RS232 serial port for data downloads into a pc or
Palm Pilot, or for quickly programming the various controller settings
with a computer in a user-friendly pull-down menu format. Up to (31) DC5500
Controllers can be linked to a single LiquiComm Communications Module for
remote communications on a standard analog phone line. The DC5500 can be used
with a LiquiComm Communications Module and the LMI DataComm Software as a
complete information management system for remote cooling tower accounts.
Back to Top
|
DC4500 Cooling Tower
Controller
The DC4500 is a bleed and feed
cooling tower controller with dual biocide timers. Standard features include;
four feed modes (Feed & Bleed, % of Time, % of Bleed, Flowmeter Pulse),
intermittent or continuous sampling, uS or PPM display, flow totalizer, manual
test modes, temperature display, biocide cycle of 7, 14, or 28 days, biocide
lockout, and conductivity or time-based biocide prebleed. Programming is simple
and is accomplished with only three keys. The backlit liquid crystal display
and LEDs provide a visual indication of operating conditions and equipment
status.
Back to Top
|
DC4000 Cooling
Tower/Boiler Controller
The DC4000 may be programmed as a
bleed and feed cooling tower controller or boiler controller. Standard features
include; four feed modes (Feed & Bleed, % of Time, % of Bleed, Flowmeter
Pulse), intermittent or continuous sampling, uS or PPM display, flow totalizer,
and manual test modes. The boiler mode includes a time-trap sampling method
that prevents the flashing problems that are so common in boilers. Programming
is simple and is accomplished with only three keys. The backlit liquid crystal
display and LEDs provide a visual indication of operating conditions and
equipment status.
Back to Top
|
|
AC4000/5000 Cooling Tower Controller
These new analog cooling tower
controllers bring state-of-the-art technology to the entry-level controller
market. The AC4000 is a simple, low cost feed and bleed controller. The AC5000
features three selectable feed options (Limit, % of Time, Flowmeter Pulse).
Both controllers feature rugged, iron vane meters and a clear, lockable cover.
Back to Top
|
DP5000 pH Controller
The DP5000 pH Controller is
designed for a variety of industrial pH applications including water treatment,
metal finishing, PCB manufacturing and waste treatment. It provides on/off or
proportional (pulse) control of metering pumps for addition of acid or base.
Level and flow inputs and alarm outputs are standard. An advanced menu includes
special features such as the solenoid dump valve control for batch treatment
and a Point 3 (inflection point) adjustment for fine tuning the
control profiles of the metering pumps. 4-20mA output is optional.
Back to Top
|
DR5000 ORP Controller
The DR5000 ORP Controller is very similar
to the DP5000 described above, however, it is designed to control LMI Metering
Pumps for the addition of oxidizing and reducing agents. It shares the same
features and options as the DP5000 and is often used in water and wastewater
treatment, fruit processing and metal finishing.
Back to Top
|
FS5000 Flow Switch
Controller
The FS5000 Flow Switch
Controller is designed for use in applications that require flow/no-flow
control of metering pumps and other devices. It includes a flow switch and
three (3) 115V receptacles that are powered with flow and one (1) 115V service
receptacle. Power indicator light, flow indicator light and test switch are
included.
Back to Top
|